Tap Changer Activity Signature Analysis

TASA® Diagnostic Program

A cost-effective way to evaluate the condition of load tap changers and regulators — catching wear before it causes a transformer failure.

What the TASA® Diagnostic Program Includes

Full data integration, 1 condition rating.

TJ|H2b’s Tap Changer Activity Signature Analysis (TASA®) provides a comprehensive evaluation of your load tap changer’s (LTC) mechanical and electrical condition — combining dissolved gas, particle, and fluid quality data into a single condition rating. Conventional LTC maintenance cycles run 4–8 years, but TASA® is performed annually, closing the gap between fixed schedules and when problems actually emerge. 

Benefits of TASA®

Early Detection

Conventional LTC maintenance cycles run 4–8 years. Annual TASA® testing catches wear long before that window closes.

Failure Reduction

Maintenance personnel can best focus on suspect units first, cutting LTC failures and the transformer damage they can cause.

Improved ROI

Savings come primarily from fewer failures and reduced labor — not from testing every unit on the same fixed schedule.

Honest Testing & Analysis

We don't offer repair or maintenance services. Our value is honest analysis, plus a consultation to interpret results and guide your next move.

How TASA® Supports Asset Managers

What Your Condition Rating Means

Every TASA® report returns a Code 1 through 4* rating. These codes are a starting point to determine how much testing is required and if condition-based maintenance or immediate action is needed.

Once you receive your report, TJ|H2b offers free, 24/7 consultation services to help interpret results and provide guidance. 

All parameters within acceptable limits. Retest within 12 months.
Onset of fault activity or oil degradation is evident. Retest within 6 months.
Substantial development of fault and/or deteriorating oil quality. Retest within 3 months.
Serious fault activity and/or very poor oil quality. Further investigative action required. Retest within 14 days.
Urgent action required. Retest immediately. Subject to confirmation via repeat sample, an internal inspection may be required; proceed immediately and with caution.

Frequently Asked Questions About TASA®

After performing a TASA® analysis on your tapchanger, you will receive a condition rating. The recommended sampling interval ranges from ‘immediately’ to ‘annually’, depending on the condition of your unit. Please refer to the scoring methodology or reach out to TJ|H2b for further explanation on recommended intervals.

TASA® condition codes, in general, indicate the following+:

  • Code 1: All parameters within acceptable limits. Retest within 12 months.
  • Code 2: Onset of fault activity or oil degradation is evident. Retest within 6 months.
  • Code 3: Substantial development of fault and/or deteriorating oil quality. Retest within 3 months.
  • Code 4: Serious fault activity and/or very poor oil quality. Further investigative action required. Retest within 14 days.
  • Code 4:* Urgent action required. Retest immediately. Subject to confirmation via repeat sample, an internal inspection may be required, proceed immediately and with caution.

+Some variations of the recommended mitigations or retest intervals may occur at the discretion of the laboratory based on information provided. With tapchangers, we are dealing with a complex subject involving a number of variables. As such, general “rules of thumb” with regard to sampling intervals cannot be applied in every case. A number of other factors must be taken into consideration, such as:

  • Service history 
  • Maintenance history
  • Model type
  • Age
  • Number of operations
  • Criticality

As such, the appropriate action is up to the discretion of the Asset Manager who is best placed to take other influencing factors into account according to established internal procedures. Our codes and recommendations, while based on a vast amount of experience as well as guidelines published by IEEE and other standards bodies, are to be taken only as useful guides.

A Tapchanger Activity Signature Assessment (TASA®) includes a condition rating, diagnostics, and potential remediation actions where applicable. Upon receipt of the report from TJ|H2b, we recommend that results and diagnostics are reviewed promptly, following internal procedures. If further support is needed, TJ|H2b offers free, 24/7 consultation services to help you understand reports and provide guidance.

TJ|H2b recommends following the latest revision of ASTM D923 (Standard Practices for Sampling Electrical Insulating Liquids) or an equivalent standard in order to ensure consistent, high-quality sampling practices. TJ|H2b has developed a tool to help you meet the standard and take a proper, representative sample every time: Turbulent Flush Sampling System.

Diagnose Your Tap Changer Health Today

Get a comprehensive, lab-verified read on your LTC’s condition — and a clear plan for what to do next. Request TASA® testing before wear becomes failure.

View Other Diagnostic Services

TJ|H2b has an entire suite of equipment-specific utility diagnostics, oil/gas sampling, and consultation services. For more information, select a diagnostic program below: